Pressure loss in the flow-through drinking water heater
The pressure loss in the flow-through drinking water heater must be taken into account when dimensioning the consumption lines (PWC/PWH) and accordingly when calculating the delivery pressure of the circulation pump(s). A misjudgement can lead to considerable malfunctions both in meeting demand and in ensuring sufficient temperatures in the circulation system.
A known operating point with a given pressure difference (Δpg) and a given flow rate (Vg) is required for the calculation. These values must be specified by the manufacturer of the flow-through drinking water heater.
|
Symbol or abbreviation: |
ΔpD-TE |
|
Usual unit: |
hPa |
|
Equation: |
|